Figure 28: Expanding The Status Messages Window; Figure 29: Status Messages In The Application Window Of The Parameterization Dialog; Table 32: Status Messages - Possible Status Messages With Additional Information - WAGO 750-496 Manual

8ai 0/4-20ma s.e., 8-channel analog input; 0/4-20 ma, single-ended
Hide thumbs Also See for 750-496:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-496 8AI 0/4-20mA S.E.
Click the button to expand the Status Messages window at the bottom of the
parameterization dialog to display the status messages.

Figure 28: Expanding the Status Messages Window

The following status messages with corresponding additional information are
displayed:
Table 32: Status Messages – Possible Status Messages with Additional Information
Status message
Measurement range overflow
Measurement range underflow
User-defined limiting value
overrange
User-defined limiting value
underrange
Short circuit
Wire break
Channel deactivated
Measured values in permissible
range
The status messages are displayed with assignment of the relevant I/O module
channels.

Figure 29: Status Messages in the Application Window of the Parameterization Dialog

Click the [Delete] button to clear the status message history. The history is
automatically cleared if you interrupt the connection to the I/O module or close
the parameterization dialog.
Error type
Channel
Warning
x
Warning
x
Warning
x
Warning
x
Error
x
Information
x
Error
x
Information
x
Information
x
Information
x
Commissioning
63
Status byte
0x42
0x41
0x04
0x08
0x50
0x00
0x60
0x00
0x00
0x00
Manual
Version 1.2.2