Fault Safe Module Parameters (F-Parameters) - WAGO 750-370 Manual

Modular i/o-system fieldbus coupler profinet io
Hide thumbs Also See for 750-370:
Table of Contents

Advertisement

68 •
PROFINET IO 750-370
I/O Device Configuration
3.1.3.3.3

Fault Safe Module Parameters (F-Parameters)

Fault safe I/O modules require the standardized PROFIsafe configuration to
ensure a safe exchange of productive data.
Parameter
F_Check_iPar
F_SIL
F_CRC_Length
F_Par_Version
F_Source_Add
F_Dest_Add
F_WD_Time
Setting
*1)
NoCheck
*1)
SIL3
*1)
3-Byte-CRC
*1)
1
1 ... 65534
1 ... 1022
*2)
100
1 ... 10000
*1) Fixed settings
*2) Presettings
Description
There are no individual parameters
contained in the F-parameters that
have to be checked.
The module complies with the safety
catagory 3.
The productive data transfer is
safeguarded using a 3 byte CRC in
case of PROFINET IO.
all outputs maintain the last valid
value
The F-Source address addresses the
F-Host.
The F-Target address addresses the
F-Device.
The F-Watchdog monitors the data
exchange between the F-Host and F-
Device. The settings are carried out
in milliseconds.
WAGO-I/O-SYSTEM 750
PROFINET IO

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents