WAGO-I/O-SYSTEM 750
750-484 2AI 4-20mA HART Ex i
coupler/controller, for the "DP slave address" in the new view.
Confirm your entry by clicking [Close].
11.
Use the mouse to select the communications DTM in the tree structure and
right click on Configuration in the context menu.
A dialog window opens with three registers: Device Information, Module
Configuration, and Parameterization.
Figure 28: Dialog Window 750-333 Configuration, Register Device Information
12.
Select the register Module Configuration and identify for Slot(2) ... Slot(x)
which module is physically plugged in to its fieldbus node. Pay attention to
all I/O modules that deliver process data in the process image.
Slot(1) has been predefined with the fieldbus coupler/controller.
For module configuration, a drop down menu of all available I/O modules
can be found in the Module column.
After the node configuration is complete, confirm by clicking [Apply].
Commissioning
77
Manual
Version 1.4.0