5
Data Display
5.2
Attribute Specification Memory
Overview
The macro command CHG_DATA was previously required to change any numerical data display
attributes during the RUN mode of MONITOUCH. Meanwhile for character display, no attribute
change macro command was provided.
However, the attribute specification memory explained in this section helps change those attributes
(the number of digits, decimal point, display type, text color, the number of bytes, or background color)
easily for numerical data and character displays while MONITOUCH is in the RUN mode.
Example: Numerical data display D100 (no transparency)
Attribute specification memory
Decimal point:
Text color:
Background color:
Display type:
D100
D200
D201
D202
D203
<Room Temperature Check>
315
D100
Applicable Items
• Numerical data display → number of digits/decimal point/display type/text color/background color
• Character display
* Attribute specification memory is not available with table data display, data sampling,
graphic library, and data sheet (but available with expanded data sheet).
5-4
Decimal point: 0 → 1, Text color: black → red, Background color: white → yellow
D200
D201
D202
D203
315
(No decimal point)
0
(Black)
0
(White)
7
(DEC w/o sign)
0
→ number of bytes/text color/background color
315
D100
D200 = 1
1
D200
D201 = 2
2
D201
D202 = 6
D202
6
D203
0
<Room Temperature Check>
31.5
<Room Temperature Check>
13B
(1 decimal place)
(Red)
(Yellow)
(DEC w/o sign)
The display now
includes one decimal
place and shows
red-colored text on
yellow-colored
background.
D203 = 3
The display type is
switched from DEC
to HEX.
The setting for one
decimal place
(D200 = 1) is invalid.