IP Address Setting of the V8
To use the Ethernet functions, it is necessary to set the IP addresses. The IP address can be set
either in: setting it through the screen data or selecting a registered network table number on
MONITOUCH.
Method 1: Setting within Screen Data
Set the IP addresses within the screen data.
1. Select [System Setting] → [Ethernet Communication] → [Local Port IP Address]. The [IP Address
Setting] dialog is displayed.
2. Check [
Set IP] and make the settings.
Select IP Address from
Network Table
*1
IP address
*1
Default Gateway
*1
Subnet Mask
*1
Port No.
Send Time Out
Retrials
Memory Protect
*1 For more information on the setting items, refer to the V8 Series Connection Manual.
This is valid when the IP address of the V8 has been registered in
the network table. An IP address can be selected from network
table No. 0 to 99.
Set the IP address of the V8.
Set the default gateway.
Set the subnet mask.
When this box is not checked, the subnet mask is automatically
recognized based on the extreme left byte of the IP address.
Example
When the IP address is "172.16.200.185", "255.255.0.0" is set.
When the IP address is "192.168.1.185", "255.255.255.0" is set.
Set a port number (1024 - 65535). (except for "8001")
Specify the timeout time to be used when sending the
EREAD/EWRITE macro command.
0 - 255
Specify the maximum number of retrials to be attempted in the
case a timeout occurs.
Check this box when disabling data writing from a computer or
another port.
20
MES Interface Function
20-9
20