Setting Procedure
In this section, a graph that shows four lines (Nos. 0 - 3) is used and how to show only two of them
(graph Nos. 0 and 1) with the PLC memory address D10000 is explained.
1. Click on the trend sampling display area to display the item dialog.
2. Open the [Detail] tab window and check [
address D10000.
Use Control
This memory address is associated with showing or hiding graph line
Memory
Nos. 0 - 15.
(Word designation)
Each graph line is shown and hidden when the corresponding bit is set
(ON) and reset (OFF).
Process Cycle
Reading the data at the control memory address occurs according to this
(High Speed, Low
cycle setting. When [Refresh] is selected, the graph is redrawn at the
leading edge (0 → 1) of bit 15* at "n + 1" in the read area or in accordance
Speed, Refresh)
with the macro command TREND_REFRESH*.
3. Transfer the screen data to the V8 series.
When bits 0 and 1 are set (ON) at D10000, only graph line Nos. 0 and 1 are drawn.
8.2
Use Control Memory]. Select the PLC memory
MSB
15
• •
• •
• •
• •
• •
Graph line No. 15
* For more information, refer to the following manuals respectively.
Read area → V8 Series Reference Manual
TREND_REFRESH → V Series Macro Reference Manual
Trend Sampling Graph Show/Hide Function
• •
• •
• •
• •
04
03
02
Graph line No. 3
Graph line No. 2
Graph line No. 1
Graph line No. 0
8
LSB
01
00
1: Show
0: Hide
8-3