Connection Of The High Power Factor Converter (Fr-Hc2) - Mitsubishi Electric FR-CS82S-025 Instruction Manual

Hide thumbs Also See for FR-CS82S-025:
Table of Contents

Advertisement

2.8.2
Connection of the high power factor converter (FR-
HC2)
When connecting the high power factor converter (FR-HC2) to suppress power harmonics, perform wiring securely as follows.
Incorrect connection will damage the high power factor converter and the inverter.
Three-phase
AC power supply
*1
Do not connect anything to power input terminals (R/L1, S/L2, T/L3). Incorrect connection will damage the inverter.
*2
Do not install an MCCB across terminals P/+ and N/- (between terminals P and P/+ or between terminals N and N/-). Connecting the opposite
polarity of terminals N/- and P/+ will damage the inverter.
*3
Use Pr.178 to Pr.182 (Input terminal function selection) to assign the terminals used for the X10 signal or the RES signal. (Refer to
*4
Always connect terminal RDY on the FR-HC2 to a terminal where the X10 signal or MRS signal is assigned on the inverter. Always connect
terminal SE on the FR-HC2 to terminal SD on the inverter. Not connecting these terminals may damage the FR-HC2.
*5
Always connect terminals R/L1, S/L2, and T/L3 on the FR-HC2 to the power supply. Operating the inverter without connecting them will damage
the FR-HC2.
*6
Do not install an MCCB or MC across terminals (R/L1, S/L2, T/L3) on the reactor 1 and terminals (R4/L14, S4/L24, T4/L34) on the FR-HC2. Doing
so disrupts proper operation.
*7
Securely perform grounding (earthing) by using the grounding (earthing) terminal.
*8
Installation of a fuse is recommended. (Refer to the Instruction Manual of the FR-HC2.)
NOTE
• The voltage phases of terminals R/L1, S/L2, and T/L3 and the voltage phases of terminals R4/L14, S4/L24, and T4/L34 must
be matched.
• The control logic (sink logic/source logic) of the high power factor converter and the inverter must be matched. (Refer to
36).
44
2. INSTALLATION AND WIRING
2.8 Connection of stand-alone option units
Reactor1
(FR-HCL21)
MCCB
MC
*6
R/
R2/
L1
L12
S/
S2/
L2
L22
T/
T2/
L3
L32
*7
Outside box
Reactor2
(FR-HCB2)
(FR-HCL22)
R3/
*6
*6
R2/
*6
R3/
R4/
L13
L12
L13
L14
S3/
S2/
S4/
S3/
L23
L22
L23
L24
T3/
T2/
T3/
T4/
L33
L32
L33
L34
*7
ROH1
ROH2
88R
88S
*7
High power
factor converter
(FR-HC2)
Inverter
*1
R/L1
R4/L14
S/L2
T/L3
S4/L24
T4/L34
Fuse
*8
P/+
P/+
*2
ROH
N/-
N/-
SD
*4
X10
RDY
*3
88R
88S
R/L1
RSO
RES
*3
S/L2
*5
SE
SD
T/L3
R1/L11
S1/L21
*7
Motor
U
V
IM
W
Earth
(ground)
*7
page
142).
page

Advertisement

Table of Contents
loading

Table of Contents