Connection Of The High Power Factor Converter (Fr-Hc2) - Mitsubishi Electric FR-CC2-H355K Instruction Manual

F800 series, fr-f802 separated converter type
Hide thumbs Also See for FR-CC2-H355K:
Table of Contents

Advertisement

Connection of stand-alone option units
2.8.2
Connection of the high power factor converter
(FR-HC2)
When connecting the high power factor converter (FR-HC2) to suppress power harmonics, perform wiring securely as shown
below. Incorrect connection will damage the high power factor converter and the inverter.
After making sure that the wiring is correct, set "rated motor voltage" in Pr.19 Rated motor voltage (under V/F control) or
Pr.83 Regenerative function selection (under other than V/F control) and "2" in Pr.30 Regenerative function selection.
∗11
MCCB
MC
Power
Supply
transformer

Remove jumpers installed in terminals R1/L11 and S1/L21 of the inverter, and connect the power supply for the control circuit to terminals
R1/L11 and S1/L21.

The voltage phases of terminals R4/L14, S4/L24, and T4/L34 and the voltage phases of terminals R/L1, S/L2, and T/L3 must be matched.

Do not install an MCCB across the terminals P/+ and N/- (across terminals P and P/+ or across N and N/-). Connecting the opposite polarity
of terminals N/- and P/+ will damage the inverter.
For the F802 series, installation of a fuse is not required.

Change the FR-HC2 parameter setting to Pr.10 RDY signal logic selection = "0" (positive logic).

Use Pr.178 to Pr.189 (input terminal function selection) to assign the terminals used for the X10 signal.
For RS-485 or any other communication where the start command is only transmitted once, use the X11 signal to save the operation mode
at the time of an instantaneous power failure.

Assign the IPF signal to an FR-HC2 terminal. (Refer to the Instruction Manual of FR-HC2.)

Always connect the FR-HC2 terminal RDY to the inverter terminal MRS(X10), and the FR-HC2 terminal SE to the inverter terminal SD. Not
connecting these terminals may damage the FR-HC2.

Always connect the R/L1, S/L2, and T/L3 terminals of FR-HC2 to the power supply. Operating the inverter without connecting them will
damage the FR-HC2.

Do not install an MCCB or MC between the reactor 1 terminals (R/L1, S/L2, T/L3) and the FR-HC2 terminals (R4/L14, S4/L24, T4/L34). It
will not operate properly.
 Securely perform grounding (earthing) by using the grounding (earthing) terminal.
 The number of connected peripheral devices differs according to the capacity. For the detail, refer to the FR-HC2 Instruction Manual.
NOTE
• The voltage phases of terminals R/L1, S/L2, and T/L3 and the voltage phases of terminals R4/L14, S4/L24, and T4/L34 must
be matched.
• The control logic (sink logic/source logic) of the high power factor converter and the inverter must be matched. (Refer to
39.)
• When using a sine wave filter with FR-HC2, select MT-BSL-HC as a reactor for the sine wave filter.
• For the parameter details, refer to the Instruction Manual (Detailed) of the FR-F800.
52
INSTALLATION AND WIRING
Limit resistor
Reactor 1
(FR-HCL21)
∗9
∗9
R2/
R/
L1
L12
S2/
S/
L2
L22
T2/
T/
L3
L32
Filter capacitors 2
∗11
(FR-HCC2)
Filter capacitor
alarm detector
(NC contact) 2
∗11
MC
Bu2
MC1
Auxiliary contact for
Buffer relay for
filter capacitor
limit MCs (NO contact) 3
alarm detectors
Limit MC
MC power
supply
stepdown
factor converter
Reactor 2
(FR-HCL22)
MC1
∗9
R3/
R4/L14
R4/
L13
L14
MC2
S4/
S3/
S4/L24
L23
L24
MC3
T3/
T4/
T4/L34
L34
L33
Limit resistor (with thermostat)
(NC contact) 3
Mini relay for filter
capacitor alarm detector
ROH
MC
MC2 MC3
Small
SD
MC1
MC2
MC3
MC
88R
Bu1
Buffer relay for driving MCs
88S
R/L1
S/L2
T/L3
R1/L11
S1/L21
High power
(FR-HC2)
∗2
R1/L11
S1/L21
∗3
P/+
P/+
N/-
N/-
∗7
RDY
X10
∗4
∗6
IPF
X11
RSO
RES
∗7
SD
SE
∗8
∗10
Inverter
U
V
M
W
∗1
Earth
(Ground)
∗5
∗10
page

Advertisement

Table of Contents
loading

Table of Contents