Standard Environment-resistive Terminals
Dimensions: DRT2-OD04CL and DRT2-OD04CL-1
6-5-6
Environment-resistive Terminals with 8 Transistor Outputs (IP67):
DRT2-OD08CL (NPN) and DRT2-OD08CL-1 (PNP)
Output Specifications
Indicators
I/O Status Indicators
Mounting hole dimensions
Item
Model
DRT2-OD08CL
Internal I/O common NPN
Output points
8 points
Rated output voltage 0.5 A/point, 4.0 A/common
20.4 to 26.4 V DC (24 V DC, −15 to +10%)
I/O power supply
voltage
Residual voltage
1.2 V max. (0.5 A DC,
between each output terminal
and G)
Leakage current
0.1 mA max.
ON delay time
0.5 ms max.
OFF delay time
1.5 ms max.
Number of circuits
8 points with one common
The I/O status indicator displays and their meanings are shown in the follow-
ing table. Refer to the section following on names of components and func-
tions for details on the location of the I/O status indicators. In the indicator
123
Two 5.3 dia. or M5
mounting holes
113±0.2
Specifications
Section 6-5
DRT2-OD08CL-1
PNP
1.2 V max. (0.5 A DC,
between each output terminal
and V)
275