Temperature Input Terminals
Setting Using the DeviceNet Configurator
1,2,3...
410
program that considers the transmission delay when the Hold Flag is turned
ON, then enables the peak/bottom hold values after a fixed time interval.
1. Double-click the icon of the Temperature Input Terminal to be set in the
Main Window and open the Edit Device Parameters Window. (From the
Maintenance Mode Window, click the right mouse button over the Slave
icon and select Parameters and Edit.)
2. Select the Tab Page for the input where peak/bottom hold is to be set, and
select Peak/Bottom Hold under the Function Choice heading.
3. To allocate the Hold Flags (output) in the default connection path, click the
General Tab and select Holding Value from the pull-down menu in the De-
fault Connection Path (Out) field.
4. Click the Download Button and then click the Reset Button to reset the
Unit.
5. Click the OK Button and exit the window.