Remote I/O Terminals with Transistors
Dimensions
Reference Data
The data shown below is based on actual measurements of samples taken
from the production line. There is some degree of variation in relay character-
istics and so this data should be used only for reference purposes.
Maximum Switching Capacity
5
4
3
2
1
0.5
DC resistive load
0.3
0.2
0.1
10
30
50
Note
1. With a current of between 2 and 3 A (common: 8 to 10 A), either ensure
that the number of points per common that simultaneously turn ON does
not exceed 4 or ensure that the temperature does not exceed 45 ° C. There
are no restrictions if the current does not exceed 2 A (common: 8 A).
2. Using at the rated current value assures normal Unit operation but does
not assure the life expectancy of the relay itself. The relay's life expectancy
varies greatly with the operating temperature, type of load, and switching
conditions, and so be sure to check the relay characteristics under the ac-
tual operating conditions.
125
AC resistive load
200
100
300
500 1000
Switching voltage (V)
Section 5-5
Life Expectancy Curve
500
120-VAC resistive load
300
30 VDC, t = 7 ms
200
240 VAC, COSφ = 0.4
120 VAC, COSφ = 0.4
100
30-VDC/240-VAC
50
resistive load
30
20
10
5
3
30 VDC, t = 40 ms
2
100 to 200 VDC
t = 7 to 40 ms
0.1
0.3
0.5
0.2
1
Switching current (A)
3
4
5
119