Analog Output Terminals

Calculation Example
7-5
Analog Output Terminals
7-5-1
DRT2-DA02 Analog Output Terminal
General Specifications
Item
Communications power supply voltage
Current consumption
Noise immunity
Vibration resistance
Shock resistance
Dielectric strength
Ambient temperature
Ambient humidity
Operating environment
Storage temperature
Mounting
Mounting strength
Screw tightening torque
Weight
Performance Specifications
Item
Output points
Output type
Output range setting method
External output allowable load resistance
Resolution
Overall accuracy
25°C
–10 to 55°C
Conversion time
Math operation
Rate of change
Cumulative counter
When using three points, and applying scaling to the first and second inputs,
and the cumulative counter to the third input, the maximum AD conversion
cycle time can be obtained by using the following formula.
Formula: 3.21 + (0.055 x 2) + 0.035 = 3.355 ms
Note With the DRT2-DA04H, the conversion cycle time is within 250 ms even when
all of the math operations are being used.
11 to 25 V DC (Supplied from the communications connector.)
120 mA max. (24 V DC)
Conforms to IEC61000-4-4. 2 kV (power lines)
10 to 150 Hz, 0.7-mm double amplitude
2
150 m/s
500 V AC for 1 min. with 1-mA sensing current (between communications
and analog circuits)
–10 to +55°C
25% to 85% (with no condensation)
No corrosive gases
–25 to +65°C
35-mm DIN Track mounting
50 N
In the direction of the Track: 10 N
M3 (power supply, I/O terminals): 0.5 N·m
150 g max.
Additional time for each point
0.030
0.035
Specifications
Specifications
Voltage output
2 points (outputs 0 and 1)
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
• DIP switch: Outputs 0 and 1 set separately.
• Configurator: Outputs 0 and 1 set separately.
1 kΩ min.
1/6,000 (full scale)
±
0.4% FS
±
0.8% FS
2 ms/ 2 points
Section 7-5
Current output
0 to 20 mA
4 to 20 mA
600 Ω max.
±
0.4% FS
±
0.8% FS
359