Troubleshooting
Model
Errors occurring in
Slaves equipped with
the External Load Dis-
connected Detection
function
DRT2-OD16SLH(-1)
DRT2-OD32SLH(-1)
DRT2-MD32SLH(-1)
Details
The Load Disconnected Flag is
going ON for outputs that are
not being used.
The Load Disconnected Flag is
going ON for an output even
though the load is connected.
A disconnection was corrected
after being detected by the
external load disconnected
detection function, but the Load
Disconnected Flag does not go
OFF.
Probable cause
The Load Disconnected
Detection function may not be
disabled for the outputs that
are not being used.
The load's current consump-
tion is too low. (The minimum
output current is 3 mA.)
The function is set for manual
reset. (The default setting is
manual reset.)
Section 9-2
Remedy
Disable the Load Discon-
nected Detection function for
outputs that are not being
used.
Disable the Load Discon-
nected Detection function.
(The function cannot detect
disconnection of this load.)
After correcting the discon-
nection, turn the I/O power
supply OFF and then ON
again.