Temperature Input Terminals
1,2,3...
434
11. Click the Fix upper adjusting Value Button. The upper limit adjustment
value will be stored in the Unit.
12. To check whether the user adjustment values have been accepted and the
Unit is operating with adjustment values different from the factory defaults,
click the right mouse button over the Slave icon and select Maintenance
Information to open the Maintenance Information Window.
Select the Tab Page for the input that was adjusted. If there is a check in
the User Adjustment Box (bottom right box), the Unit is operating with us-
er-set adjustment values.
Note
1. When checking whether or not the user adjustment values have been set
correctly, always refresh the data by clicking the Update Button in the
Maintenance Information Window's General Tab or uploading the settings
again. For details on the Maintenance Information Window, refer to 7-3
Maintenance Information Window.
2. If the correct reference voltage was not input, the adjustment values may
not be accepted.
Adjusting the DRT2-TS04T's Bias Compensation Value
1. Disconnect the reference voltage/current generator (STV) and short the
leads from the ZERO-CON (0 ° C bath).
2. After completing the wiring, wait at least 40 minutes, and click the Fix Bias
adjusting Value Button. The bias compensation value will be stored in the
Unit.
Section 7-6