DeviceNet Remote I/O Communications
Poll
Bit-Strobe
COS
Cyclic
Note If there are checks in the checkboxes but the connection path settings are left
blank, the following settings will be made automatically.
IN (Smart Slave to Master Unit)
input data
input data
generic status
generic status
Note For Slaves with outputs (and consequently output size settings), if the poll and
COS connections are used at the same time, the output size settings for poll
and COS connections must be set to the same value. Perform this setting with
the Configurator using the method below. (The default output size setting for
the COS connection is 0.)
Click the right mouse button over the Slave to be set, select Property, click
the I/O Information Tab, and then click the Edit Button. In the Edit I/O Size
Window, set the OUT Size for the poll and COS connections to the same
value.
4. Click the I/O Allocation (IN) Tab and edit the I/O allocations.
Select the Smart Slave to be set and click the Edit Button to display the
Edit I/O Allocate Window.
Set the Poll settings (indicates input data) to block 1, allocated 3300.
Set the COS settings (indicates generic data) to block 2, allocated 3500.
OUT (Master Unit to Smart Slave)
output data
Not set.
Not set.
Not set.
Section 3-2
45