Omron DRT2 SERIES DEVICENET SLAVES - OPERATION MANUAL 04-2008 Operation Manual page 323

Devicenet slaves
Hide thumbs Also See for DRT2 SERIES DEVICENET SLAVES - OPERATION MANUAL 04-2008:
Table of Contents

Advertisement

Overview of Analog Slaves
Fixed I/O Data Combinations (DRT2-AD04 and DRT2-AD04H)
I/O Data Type
Analog Data 1 + Analog Data 2
(16 input bytes)
Top/Valley Detection Timing
Flags + Generic Status Flags
(3 input bytes)
Analog Status Flags + Generic
Status Flags (5 input bytes)
Analog Data 1 + Top/Valley
Detection Timing Flags (10
input bytes)
Analog Data 1 + Top/Valley
Detection Timing Flags +
Generic Status Flags (11 input
bytes)
Fixed I/O Data Combinations (DRT2-TS04T and DRT2-TS04P)
I/O Data Type
Temperature Data 1 + Temper-
ature Data 2
16 input bytes (Normal display)
32 input bytes (1/100 display)
Top/Valley Detection Timing
Flags + Generic Status Flags
(3 input bytes)
Analog Status Flags + Generic
Status Flags (5 input bytes)
Temperature Data 1 + Top/Val-
ley Detection Timing Flags
10 input bytes (Normal display)
18 input bytes (1/100 display)
Analog Data 1 + Top/Valley
Detection Timing Flags +
Generic Status Flags
11 input bytes (Normal display)
19 input bytes (1/100 display)
Analog Output
Terminals
Input Data
Data Type
Generic Status Flags (1 input
byte)
Output Data
Data Type
Output data (4 output bytes)
302
Allocation of Analog Data 1 followed by Analog Data 2.
Allocation of the Top/Valley Detection Timing Flags followed by the
Generic Status Flags.
Allocation of the Analog Status Flags followed by the Generic Sta-
tus Flags.
Allocation of Analog Data 1 followed by the Top/Valley Detection
Timing Flags.
Allocation of Analog Data 1 followed by Top/Valley Detection Timing
Flags and then the Generic Status Flags.
Allocation of Temperature Data 1 followed by Temperature Data 2.
Allocation of the Top/Valley Detection Timing Flags followed by the
Generic Status Flags.
Allocation of the Analog Status Flags followed by the Generic Sta-
tus Flags.
Allocation of Temperature Data 1 followed by the Top/Valley Detec-
tion Timing Flags.
Allocation of Temperature Data 1 followed by Top/Valley Detection
Timing Flags and then the Generic Status Flags.
Note Data can be allocated using other data combinations, but only when an
OMRON CS/CJ-series Master Unit is used because the settings are made in
the Master Unit.
Analog Output Terminals support one type of input data and output data each.
Allocate the required data as shown in the following tables.
Used to allocate the Network Voltage Monitor Flag, the Unit Con-
duction Time Monitor Flag, and the Cumulative Counter Flag.
Used to allocate analog output data.
Details
Details
Details
Details
Section 7-1
Assembly
Instance No.
144
151
164
174
184
Assembly
Instance No.
144 (Normal dis-
play)
148 (1/100 display)
151
164
174 (Normal dis-
play)
178 (1/100 display)
184 (Normal dis-
play)
188 (1/100 display)
Assembly Instance
No.
121
Assembly Instance
No.
192

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Devicenet drt2-id08Devicenet drt2-id08-1Devicenet drt2-id16-1Devicenet drt2-od16Devicenet drt2-od08Devicenet drt2-md16 ... Show all