Temperature Input Terminals
Offset Compensation
Setting Using the DeviceNet Configurator
1,2,3...
( − 28,000 to 28,000) for two points in the scale (the 100% value and 0%
value).
Value for 100% set by user
(Scaling point 2)
Value for 0% set by user
(Scaling point 1)
Note
1. The default values are 0 and 28,000.
2. Reverse scaling, where the 0% scaling value is higher than the 100% scal-
ing value, is also supported.
The scaling function is equipped with offset compensation, which can com-
pensate for any error that occurs during scaling. The offset amount is added
to the scaled line as shown in the following diagram. The offset (error) value
can be input between
overflow does not occur. The High Limit is 7FFE hex and the Low Limit is
8000 hex.
Note The offset value can be set even when using default scaling.
Upper limit 7FFE hex
100% scaling value (32766)
0% scaling
Lower limit 8000 hex (−32768)
1. Double-click the icon of the Temperature Input Terminal to be set in the
Main Window and open the Edit Device Parameters Window. (From the
Maintenance Mode Window, click the right mouse button over the Slave
icon and select Parameters and Edit.)
Scaling value
Conversion
0%
1
28,000 to 28,000, but make sure that underflow or
Offset value
(–28,000 to
28,000)
0%
Section 7-6
Input signal range
00%
Scaled line
Input signal range
100%
407