Omron DRT2 SERIES DEVICENET SLAVES - OPERATION MANUAL 04-2008 Operation Manual page 456

Devicenet slaves
Hide thumbs Also See for DRT2 SERIES DEVICENET SLAVES - OPERATION MANUAL 04-2008:
Table of Contents

Advertisement

Temperature Input Terminals
Note
Resetting User Adjustments
If it is necessary to reset the upper limit adjustment value, lower limit adjust-
ment value, and bias compensation value to the factory defaults, click the
Default Setting Button. The settings will be returned to the factory settings.
The upper/lower limit adjustment values and bias compensation value are all
initialized at the same time.
1. The bias compensation value may not be accepted if there is a large tem-
perature difference between the Terminal Block and ZERO-CON (0 ° C
bath). If this problem occurs, correct the adjustment system by using a ZE-
RO-CON compatible with the sensor being adjusted or other means.
2. Always test the indication accuracy after making user adjustments to verify
that the adjustments are correct. Test the indication accuracy at three
points: the lower limit value, an intermediate value, and the upper limit val-
ue.
• Connect the external devices as shown in the following diagram.
• After verifying that the ZERO-CON is set to 0 ° C, set the STV's output
voltage to produce a voltage equivalent to the test voltage.
Note Always use the compensating conductors (the same kind that will be
used with the sensor being adjusted) to connect the ZERO-CON to
the DRT2-TS04T's input terminals.
ZERO-CON
(0 ° C bath)
STV
OUTPUT
Note In order to perform the adjustment procedure properly, always allow sufficient
time for temperature stabilization, as shown in the following diagram. Also
allow sufficient time for devices such as the STV, DMM, and ZERO-CON to
stabilize. Refer to each device's operating manual for details.
DRT2-TS04T
Compensating
conductors
Input (+)
Input (–)
INPUT
Section 7-6
435

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Devicenet drt2-id08Devicenet drt2-id08-1Devicenet drt2-id16-1Devicenet drt2-od16Devicenet drt2-od08Devicenet drt2-md16 ... Show all