Mounting and Wiring Environment-resistive Slaves
Wiring I/O
Compatible Connectors
288
mal shutdown, so when a Power Supply Unit with a low-capacity rating or
instantaneous shutoff overcurrent protection is used, the load short-circuit
may not be detected. Always use a Power Supply Unit with a rating of 50
W or higher if it uses dropping overcurrent protection characteristic. Always
use a Power Supply Unit with a rating of 150 W or higher if it uses intermit-
tent overcurrent protection. The current limiter will protect the transistor
even if short-circuit detection is disabled.
Connect the I/O wiring to the Environment-resistive Terminal with the XS2-
series Round Waterproof Connectors listed in the following table.
Cable with connector on one end (male plug)
Cable with connectors on both ends (socket and plug)
Connector plug assembly (male)
(Crimp-connector or solder type)
Sensors that are pre-wired with a connector can be connected directly.
Refer to the catalog or manual for details on the device's pin arrangements
before connecting any device.
XS2W-D42@-@81-A Cable with
round waterproof connector on
both ends (socket/plug)
Sensor with Connector
Sensor with Junction Connector
Note Refer to the OMRON Sensors Catalog (X42) for details on Sensor Connec-
tions and Round Waterproof Connectors (Sensor I/O Connectors).
Use one of the following OMRON Y-joints when connecting a DRT2-HD16C(-
1), DRT2-HD16CL(-1), or DRT2-MD16CL(-1) Environment-resistive Terminal
with 16 inputs to sensors or limit switches, except when the sensor has diag-
nostic output.
Y-joint with plug/socket (connector on both ends)
Y-joint with plug/socket (without cable)
XS2R-D426-@11-F Y-joint with plug/socket
(connector on both ends)
XS2R-D426-1 Y-joint with
plug/socket (without cable)
Note The XS2G Connector Plug for Custom Cable Assembly (L-shaped type) and
XS2W-series L-shaped plug type cannot be connected to a Y-joint Connector,
because these connectors will cause interference with any Connectors
located beside them.
Connector
XS2H-D421-@80-A Cable with round
waterproof connector on one end (plug)
XS2G-D4@@
Sensor with lead wires
Connector
16 inputs
Section 6-6
Model
XS2H-D421-@80-A
XS2W-D42@-@81-A
XS2G-D4@@
Model
XS2R-D426-@11-F
XS2R-D426-1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Devicenet drt2-id08Devicenet drt2-id08-1Devicenet drt2-id16-1Devicenet drt2-od16Devicenet drt2-od08Devicenet drt2-md16 ... Show all

Table of Contents