Analog Output Terminals
Item
DA conversion data
Isolation method
I/O connection method
Standard accessories
Names and Functions of Parts
Setting the Output Signal Range
Setting with the DIP
Switch
360
Communications
connector
The output range can be set using the DIP switch or the Configurator.
1
2
3
4
5
Each pin is set according to the following table.
Pin No.
1
2
3
4
5
6
7
8
Note
1. Always set pin 8 to ON if the DIP switch is used to set the range. If this pin
is OFF, the DIP switch settings will not be enabled.
2. The DIP switch settings are read when the power is turned ON.
Voltage output
–10 to 10 V range: F448 to 0BB8 hex full scale (–3,000 to 3,000)
Other ranges: 0000 to 1770 hex full scale (0 to 6,000)
±
DA conversion range:
Photocoupler isolation (between output and communications lines)
No isolation between output signal wires.
Terminal-block connection
None
Rotary switches.
Set the node address.
DIP switch
DeviceNet
Sets the output
indicators
ranges.
Removeable terminal block
6
7
8
Setting
Sets output range for Output 0
Sets output range for Output 1
Sets DA conversion data format
Range setting method
Specifications
Current output
5% FS of the above data ranges.
Specifications
Default setting: All pins OFF
Default setting: All pins OFF
ON: Signed binary
OFF: Two's complement
OFF: Use Configurator.
ON: Use DIP switch.
Default setting: OFF
Section 7-5