Analog Input Terminals
Cumulative Counter
Setting Using the DeviceNet Configurator
1,2,3...
354
9. Click the OK Button and exit the window.
The cumulative counter calculates an approximation to the integral of analog
input values over time. The cumulated value can be calculated in "count
hours" (by selecting "hours") or "count minutes" (by selecting "minutes"). The
count value is the analog input value in the industry unit obtained after scal-
ing. For example, 100.0 count hours indicates a value equivalent to an analog
input value of 100 counts continuing for one hour. The counter range for a
four-byte area (two words) for count hours or count minutes is –214,748,364.8
to +214,748,364.7. Data is displayed on the Configurator in units of 0.1 hour
or minute.
Monitor values can also be set in the Unit. When the cumulated count value
exceeds the set monitor value, the Cumulative Counter Flag in the area for
Generic Status Flags turns ON.
Analog input value
Division width
Note The following table shows the divisions for the cumulative counter.
DRT2-AD04
Unit
Hour
Minute
DRT2-AD04H
Unit
Hour
Minute
1. Double-click the icon of the Analog Slave to be set in the Main Window and
open the Edit Device Parameters Window. (From the Maintenance Mode
Window, click the right mouse button over the Slave icon and select Pa-
rameters and Edit.)
Cumulated value (count x
hour or count x minute)
Divisions
3.6 s (1/1,000 hour)
60 ms (1/1,000 minute)
Divisions
15 s (1/240 hour)
250 ms (1/240 minute)
Section 7-4
Time