Temperature Input Terminals
Setting Using the DeviceNet Configurator
1,2,3...
1. Double-click the icon of the Temperature Input Terminal to be set in the
Main Window and open the Edit Device Parameters Window. (From the
Maintenance Mode Window, click the right mouse button over the Slave
icon and select Parameters and Edit.)
2. Select the Tab Page for the input where top/valley counter is to be set, and
select Top/Valley under the Function Choice heading.
3. Select the Top/Valley Tab and select either Top Count or Valley Count
from the pull-down menu in the Count Type field.
4. A threshold count value can be set in the Threshold Top/Valley Counter
field.
5. Return to the General Tab, click the Download Button, and then click the
Reset Button to reset the Unit.
6. Click the OK Button and exit the window.