DeviceNet Explicit Messages
Explicit
Read
message
/write
Sampling
Write/
Sets the sampling cycle
Cycle Set-
Read
for obtaining the rate of
ting
change based on the
previous value.
Set in multiples of
250 ms.
(Default: 250 ms)
Cumulated
Read/
Reads the cumulated
Value Read
Reset
temperature input value.
Cumulative
Read Reads the cumulative
Counter
count status in the
Flag Read
Cumulative Counter
Flag in the area for
Generic Status Flags.
0: Counter overflow
1: Counter underflow
7: Set value overflow
Cumulative
Write/
Writes/reads the set
Counter
Read
monitor value for the
Monitor
cumulative counter.
Value Set-
ting
Cumulative
Write/
Sets the unit for the
Counter
Read
cumulative counter.
Unit Setting
0: Hour (count hours);
1: Minute (count
minutes)
Decimal
Read Reads the position of
Position
the decimal point.
Read
0000 = 0
0000.0 = 1
0000.00 = 2
Top/Valley
Read/
Reads the number of
Count Read
Reset
tops or valleys that have
been counted.
Top/Valley
Read Reads whether the top/
Count
valley count has
Threshold
exceeded the threshold
Status
value.
Read
0: Counter overflow
1: Counter underflow
7: Set value overflow
Top/Valley
Write/
Selects counting either
Counting
Read
tops or valleys.
Selection
Count tops = 0
Count valleys = 1
Top/Valley
Write/
Sets the threshold value
Count
Read
to compare with the top/
Threshold
valley count.
Set
488
Function
Service
code
Write:
10 Hex
Read:
0E Hex
Read:
0E Hex
Reset:
35 Hex
0E Hex
Write:
10 Hex
Read:
0E Hex
Write:
10 Hex
Read:
0E Hex
0E Hex
Read:
0E Hex
Reset:
35 Hex
0E Hex
Write:
10 Hex
Read:
0E Hex
Write:
10 Hex
Read:
0E Hex
Command
Class
Instance
Command data
ID
ID
Attribute
ID
31 Hex 01 to 04
90 Hex
Hex
31 Hex 01 to 04
91 Hex
Hex
31 Hex 01 to 04
92 Hex
Hex
31 Hex 01 to 04
93 Hex
Hex
31 Hex 01 to 04
94 Hex
Hex
31 Hex 01 to 04
A3 Hex
Hex
31 Hex 01 to 04
A9 Hex
Hex
31 Hex 01 to 04
AA Hex
Hex
31 Hex 01 to 04
AB Hex
Hex
31 Hex 01 to 04
AC Hex
Hex
Appendix A
Response
Data
2 bytes
2 bytes
(250 to 65550)
(250 to 65550)
---
4 bytes
(−214748364.8
to
214748364.7)
---
1 byte
4 bytes
4 bytes
1 byte
1 byte
---
1 byte
---
4 bytes
---
1 byte
1 byte
1 byte
4 bytes
4 bytes

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Devicenet drt2-id08Devicenet drt2-id08-1Devicenet drt2-id16-1Devicenet drt2-od16Devicenet drt2-od08Devicenet drt2-md16 ... Show all

Table of Contents