Omron DRT2 SERIES DEVICENET SLAVES - OPERATION MANUAL 04-2008 Operation Manual page 389

Devicenet slaves
Hide thumbs Also See for DRT2 SERIES DEVICENET SLAVES - OPERATION MANUAL 04-2008:
Table of Contents

Advertisement

Analog Output Terminals
7-5-3
Functions and Setting Methods
Scaling
Default Scaling
368
The details of each bit are shown in the following table.
Bit
Abbrevia-
Name
tion
0
---
---
1
---
---
2
NPW
Network Power Voltage Mon-
itor Flag
3
RHW
Unit Conduction Time Moni-
tor Flag
4
CCW
Analog Cumulative Counter
Flag
5
MRF
Unit Error Flag
6
---
---
The following format is used when the Generic Status Flags are allocated,
starting from the rightmost byte of the Master
Word
15
+1
The default setting is used to perform AD conversion, converting analog out-
put values that have been scaled to a count of 0 to 6,000 into corresponding
digital values in the output signal range. Scaling can be used to change
scaled values that correspond to the output signal range into other values
required by the user (industry unit values). Scaling also eliminates the need
for ladder programming in the Master to perform math operations. The follow-
ing two methods of scaling can be used.
Default scaling converts analog output values into voltage or current values.
The units used are mV or
formed according to the output range, as shown in the following table.
Output
0 to 5 V
0 to 10 V
range
100%
5,000 mV
10,000
mV
0%
0000 mV
0000 mV
Off-wire ---
---
.
8 7
µ
A. When default scaling is selected, scaling is per-
1 to 5 V
–10 to 10 V
5,000 mV
10,000 mV
1,000 mV
–10,000 mV 0000
7FFF hex
---
Section 7-5
Details
Reserved. (Always 0.)
Reserved. (Always 0.)
Turns ON when the Network
power level drops below the
set monitor value.
Turns ON when the Unit ON
time exceeds the set monitor
value.
Turns ON when any of the
cumulated analog values
exceeds the set monitor
value.
Turns ON when analog con-
version stops due to a Unit
error.
Reserved. (Always 0.)
Generic Status Flags
0 to
4 to
20 mA
20 mA
µ
µ
20,000
A 20,000
µ
µ
A
4,000
---
7FFF hex
0
A
A