Omron DRT2 SERIES DEVICENET SLAVES - OPERATION MANUAL 04-2008 Operation Manual page 363

Devicenet slaves
Hide thumbs Also See for DRT2 SERIES DEVICENET SLAVES - OPERATION MANUAL 04-2008:
Table of Contents

Advertisement

Analog Input Terminals
Setting Using the DeviceNet Configurator
1,2,3...
342
program that considers the transmission delay when the Hold Flag is turned
ON, then enables the peak/bottom hold values after a fixed time interval.
1. Double-click the icon of the Analog Slave to be set in the Main Window and
open the Edit Device Parameters Window. (From the Maintenance Mode
Window, click the right mouse button over the Slave icon and select Pa-
rameters and Edit.)
2. Select the Tab Page for the input where peak/bottom hold is to be set, and
select Peak/Bottom Hold under the Function Choice heading.
3. To allocate the Hold Flags (output) in the default connection path, click the
General Tab and select Holding Value from the pull-down menu in the De-
fault Connection Path (Out) field.
4. Click the Download Button and then click the Reset Button to reset the
Unit.
5. Click the OK Button and exit the window.
Section 7-4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Devicenet drt2-id08Devicenet drt2-id08-1Devicenet drt2-id16-1Devicenet drt2-od16Devicenet drt2-od08Devicenet drt2-md16 ... Show all

Table of Contents