Omron DRT2 SERIES DEVICENET SLAVES - OPERATION MANUAL 04-2008 Operation Manual page 267

Devicenet slaves
Hide thumbs Also See for DRT2 SERIES DEVICENET SLAVES - OPERATION MANUAL 04-2008:
Table of Contents

Advertisement

Advanced Environment-resistive Terminals
I/O Status Indicators
246
Item
ON voltage
9 V DC min. (between each
input terminal and V)
OFF voltage
5 V DC max. (between each
input terminal and V)
OFF current
1 mA max.
Input current
3 mA min./point (at 11 V DC)
11 mA max./point (at 24 V DC)
Sensor power supply
Maximum communications power supply voltage: +0 V
voltage
Minimum communications power supply voltage: −1.5 V
ON delay time
1.5 ms max.
OFF delay time
1.5 ms max.
Number of circuits
8 points with one common
The I/O status indicator displays and their meanings are shown in the follow-
ing table. Refer to the section following on names of components and func-
tions for details on the location of the I/O status indicators. In the indicator
name "1-A," the "1" indicates the connector number, and the "A" indicates that
it is an I/O status indicator.
Indicator
Color
1-A
Yellow
Red
Red
2-A
Yellow
Red
Red
3-A
Yellow
Red
Red
4-A
Yellow
Red
Red
5-A
Yellow
Red
Red
6-A
Yellow
Red
Red
7-A
Yellow
Red
Red
8-A
Yellow
Red
Red
Specifications
Status
ON
Input 0 is ON.
ON
The sensor power of connector 1 has
shorted.
Flashing
The sensor of connector 1 is disconnected.
ON
Input 1 is ON.
ON
The sensor power of connector 2 has
shorted.
Flashing
The sensor of connector 2 is disconnected.
ON
Input 2 is ON.
ON
The sensor power of connector 3 has
shorted.
Flashing
The sensor of connector 3 is disconnected.
ON
Input 3 is ON.
ON
The sensor power of connector 4 has
shorted.
Flashing
The sensor of connector 4 is disconnected.
ON
Input 4 is ON.
ON
The sensor power of connector 5 has
shorted.
Flashing
The sensor of connector 5 is disconnected.
ON
Input 5 is ON.
ON
The sensor power of connector 6 has
shorted.
Flashing
The sensor of connector 6 is disconnected.
ON
Input 6 is ON.
ON
The sensor power of connector 7 has
shorted.
Flashing
The sensor of connector 7 is disconnected.
ON
Input 7 is ON.
ON
The sensor power of connector 8 has
shorted.
Flashing
The sensor of connector 8 is disconnected.
Section 6-4
9 V DC min. (between each
input terminal and G)
5 V DC max. (between each
input terminal and G)
Meaning