Temperature Input Terminals
Temperature Ranges
by Input Type
DRT2-TS04T
DRT2-TS04P
382
3. Select the desired sensor from the pull-down menu in the Sensor Type
field.
4. Return to the General Tab, click the Download Button, and then click the
Reset Button to reset the Unit.
5. Click the OK Button and exit the window.
The input type can be set with the DIP switch or Configurator. The following
tables show the temperature ranges for each input type.
Input type
Temperature range (°C)
R
0 to 1,700
S
0 to 1,700
−200 to 1,300
K1
K2
0.0 to 500.0
−100 to 850
J1
J2
0.0 to 400.0
−200.0 to 400.0
T
E
0 to 600
−100 to 850
L1
L2
0.0 to 400.0
−200.0 to 400.0
U
−200 to 1,300
N
W
0 to 2,300
B
100 to 1,800
PL2
0 to 1,300
Input type
Temperature range (°C)
−200.0 to 850.0
PT
−200.0 to 650.0
JPT
−200.0 to 200.0
PT2
−200.0 to 200.0
JPT2
Section 7-6
Temperature range (°F)
0 to 3,000
0 to 3,000
−300 to 2,300
0.0 to 900.0
−100 to 1,500
0.0 to 750.0
−300.0 to 700.0
0 to 1,100
−100 to 1,500
0.0 to 750.0
−300.0 to 700.0
−300 to 2,300
0 to 4,100
300 to 3,200
0 to 2,300
Temperature range (°F)
−300.0 to 1,500.0
−300.0 to 1,200.0
−300.0 to 380.0
−300.0 to 380.0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Devicenet drt2-id08Devicenet drt2-id08-1Devicenet drt2-id16-1Devicenet drt2-od16Devicenet drt2-od08Devicenet drt2-md16 ... Show all

Table of Contents