Functions of General-purpose Slaves and Environment-resistive Slaves
Setting Using the
DeviceNet
Configurator
Basic I/O Unit Combined with Expansion Unit, Sensor Connector I/O Terminal, or Environment-
resistive I/O Terminal
1,2,3...
70
formation to be held in the ladder program.
ON
Input
OFF
ON
Output
OFF
ON
Operation Time Flag
OFF
Be careful of the following point when using a Unit that can use the operation
time monitor function (i.e., Basic I/O Unit and Expansion Unit, Sensor Con-
nector I/O Terminal, Three-tier Terminal Block, MIL Connector Terminal, or
Screw-less Clamp Terminal).
2. The operating time is recorded as soon as the time has been measured
from when the output changes to ON to when the input changes to ON.
The time until the next output changes to ON, however, continues being
measured internally, and the measurement value will be refreshed if the in-
put changes to ON again before the next output changes to ON. (When an
input occurs during the operation time for a reciprocating operation such
as a cylinder, the measurement for the operating time (outward path) may
be refreshed during the return time (return path).
When an output changes to ON twice consecutively, and is followed by the
input changing to ON, the time is measured from when the second output
changes to ON until the input changes to ON.
ON
Output
OFF
ON
Input
OFF
Operation Time
Monitor
(Previous
value)
ON
Output
OFF
ON
Input
OFF
Output; Input; Measures
this time period.
The method used to set values from the DeviceNet Configurator (Ver. 2.20 or
later) is described here.
1. Turn ON the power to the DRT2-series Smart Slave.
Monitor value
Within monitor
exceeded
value range
t1
t3
t2
t1
t2
Section 4-3
t3