No.
o4-05
n
o4-07: DC Bus Pre-Charge Relay Maintenance Setting
Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expected
performance life. Reset this value to 0 after replacing the bypass relay.
Note:
The actual maintenance time will depend on the environment where the drive is used.
No.
o4-07
DC Bus Pre-charge Relay Maintenance Setting
n
o4-11: U2, U3 Initialization
Resets the fault trace and fault history monitors (U2-oo and U3-oo).
Note:
Initializing the drive using A1-03 does not reset these monitors.
No.
o4-11
Setting 0: No Action
The drive keeps the previously saved record concerning fault trace and fault history.
Setting 1: Reset Fault Data
Resets the data for the U2-oo and U3-oo monitors. Setting o4-11 to 1 and pressing the ENTER key erases fault data and
returns the display to 0.
n
o4-12: kWh Monitor Initialization
Resets the electric power (U9-01 to U9-03) and regenerative power (U9-04 to U9-06). Resets electric power rate (U9-07 to
U9-10) and regenerative power rate (U9-11 to U9-14).
No.
o4-12
Setting 0: No Action
Setting 1: Reset kWh Data
n
o4-13: Number of Run Commands Counter Initialization
Resets the Run command counter displayed in U4-02. Initializing the drive or cycling the power does not reset this monitor.
No.
o4-13
Number of Run Commands Counter Initialization
Setting 0: No Action
The Run command data are kept.
Setting 1: Number of Run Commands Counter
Resets the Run command counter. The monitor U4-02 will show 0. Setting o4-13 to 1 and pressing the ENTER key erases the
counter value and returns the display to 0.
n
o4-19: Power Unit Price
Sets the price per 1 kWh to calculate the power rate displayed for total consumed power (U9-07 to U9-10) and total regenerated
power (U9-11 to U9-14).
No.
o4-19
u

q: DriveWorksEZ Parameters

These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Name
Capacitor Maintenance Setting
Name
Name
U2, U3 Initialization
Name
kWh Monitor Initialization
Name
Name
Power Unit Price
5.10 o: Operator Related Settings
Setting Range
0 to 150%
Setting Range
0 to 150%
Setting Range
0, 1
Setting Range
0, 1
Setting Range
0, 1
Setting Range
0.00 to 650.00
Default
0%
Default
0%
Default
0
Default
0
Default
0
5
Default
000.00
349