B5: Pid Control - YASKAWA GA800 Programming Manual

Ac drive for industrial applications
Table of Contents

Advertisement

b5: PID Control

No.
Name
(Hex.)
b5-01
PID Mode Setting
(01A5)
b5-02
Proportional Gain (P)
(01A6)
RUN
b5-03
Integral Time (I)
(01A7)
RUN
b5-04
Integral Limit
(01A8)
RUN
b5-05
Derivative Time (D)
(01A9)
RUN
b5-06
PID Output Limit
(01AA)
RUN
b5-07
PID Offset Adjustment
(01AB)
RUN
b5-08
PID Primary Delay Time
Constant
(01AC)
RUN
Expert
b5-09
PID Output Level
Selection
(01AD)
b5-10
PID Output Gain Setting
(01AE)
RUN
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of PID control.
0 : Disabled
1 : Standard
2 : Standard (D on feedback)
3 : Fref + PID Trim
4 : Fref + PID Trim (D on feedback)
5 : Same as 7series & prior, b5-01=1
6 : Same as 7series & prior, b5-01=2
7 : Same as 7series & prior, b5-01=3
8 : Same as 7series & prior, b5-01=4
Note:
Use settings 5 to 8 when the drive is a replacement for a previous generation drive.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the proportional gain (P) that is applied to PID input.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the integral time (I) that is applied to PID input.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the upper limit for integral control (I) as a percentage of the Maximum Output
Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the derivative time (D) for PID control. This parameter adjusts system responsiveness.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the maximum possible output from the PID controller as a percentage of the
Maximum Output Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset for the PID control output as a percentage of the Maximum Output
Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the primary delay time constant for the PID control output. Usually it is not necessary
to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the polarity of the PID output.
0 : Normal Output (Direct Acting)
1 : Reverse Output (Reverse Acting)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the amount of gain to apply to the PID output.
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
1.5 b: Application
Default
Ref.
(Range)
0
227
(0 - 8)
1.00
228
(0.00 - 25.00)
1.0 s
228
(0.0 - 360.0 s)
100.0%
228
(0.0 - 100.0%)
0.00 s
229
(0.00 - 10.00 s)
100.0%
229
(0.0 - 100.0%)
0.0%
229
(-100.0 - +100.0%)
0.00 s
229
(0.00 - 10.00 s)
0
229
(0, 1)
1.00
229
(0.00 - 25.00)
27
1