9.3.7.7

Inhibiting AOP LOCAL mode

Settings: Menu – Commissioning/Service – AOP settings – Control settings
Inhibit AOP LOCAL mode (factory setting: No)
● Yes: Deactivates the "Control via operator panel" function, thereby disabling the
● No: Activates the LOCAL/REMOTE key.
9.3.7.8

Acknowledging errors via the AOP

Settings: Menu – Commissioning/Service – AOP settings – Control settings
Acknowledge error from the AOP (factory setting: Yes)
● Yes: Errors can be acknowledged via the AOP.
● No: Errors cannot be acknowledged via the AOP.
9.3.7.9

Timeout monitoring

In "LOCAL" mode or if "OFF in REMOTE" is active, the drive is shut down after 1 s. if the
data cable between the AOP and drive is disconnected.
9.3.7.10

Operator inhibit lock/Parameters disable

Operator inhibit lock/Parameters disable
To prevent the control keys from being operated and parameters from being changed
unintentionally, you can activate an operator inhibit lock/parameters disable using a key-
operated pushbutton. Two key icons appear at the top right of the display when these safety
inhibits are enabled.
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
LOCAL/REMOTE key.
Note
LOCAL functionality can also be inhibited on the drive by means of the p0806 parameter
(BI: Inhibit master control).