Note
There must be no electrical connection between the encoder system housing and the
encoder system electronics. If this is not carefully observed, under certain circumstances the
system will not be able to reach the required interference immunity level (there is then a
danger of equalization currents flowing through the electronics ground).
CAUTION
When the encoder system is connected via terminals, make sure that the cable shield is
connected to the component.
Connecting cables to temperature sensors must always be installed with shielding. The
cable shield must be connected to the ground potential at both ends over a large surface
area. Temperature-sensor cables that are routed together with the motor cable must be
twisted in pairs and shielded separately.
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
CAUTION
Additional system components
7.2 Sensor Module Cabinet-Mounted SMC30