Additional system components
7.1 Option Board: Communication Board Ethernet CBE20
Table 7- 4
Meaning of the OPT LED on the Control Unit
LED
Color
OPT
Green
Red
Orange
174
Status
OFF
Electronics power supply is missing or outside permissible
tolerance range.
Communication Board either defective or not inserted.
Continuous
Communication Board is ready and cyclic communication
light
is taking place.
0.5 Hz
The Communication Board is ready, but cyclic
flashing light
communications is not running.
Possible causes:
At least one fault is present.
Communication is being established.
Continuous
Cyclic communication via PROFINET has not yet been
light
established. However, non-cyclic communication is
possible. SINAMICS waits for a parameterizing/configuring
telegram
0.5 Hz
The firmware update into the CBE20 has been completed
flashing light
with an error.
Possible causes:
The CBE20 is defective.
The memory card for the Control Unit is defective.
CBE20 cannot be used in this state.
2 Hz
There is a communications error between the Control Unit
flashing light
and the CBE20.
Possible causes:
Board was withdrawn after booting.
The board is defective
0.5 Hz
Firmware is being updated.
flashing light
Description, cause
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
Remedy
Correctly insert the
board, if required,
replace.