5.4.5.4

Selecting the control mode

Suitable applications and typical control properties
U/f control or FCC (flux current con‐
trol) without an encoder
Application
Horizontal conveyor technology
examples
(conveyor belts, roller conveyors,
chain conveyors)
Pumps, fans, and compressors with
flow characteristic
Motors that
can be oper‐
ated
The rated current of the motor must lie in the range of 13 % ... 100 % of the rated current of the converter.
Properties
Responds to speed changes with a
of closed-
typical settling time of
loop motor
100 ms ... 200 ms
control
Responds to load surges with a typ‐
ical settling time of 500 ms
U/f and FCC are suitable for the fol‐
lowing cases:
– For power-up times 0 → rated
speed > 2 s
– For applications with increasing
load torque without load impul‐
ses
The closed-loop control is insensi‐
tive to inaccurate motor data set‐
tings, e.g. the motor temperature
Max. output
frequency
Torque con‐
Closed-loop torque control not possible Torque control for speeds > 15 %
trol
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Induction motors
550 Hz
Vector control without an en‐
coder
Horizontal conveyor technolo‐
gy (conveyor belts, roller con‐
veyors, chain conveyors)
Extruder
Centrifuges
Pumps and compressors with
displacement machines
Induction motors
Encoderless 1FK7 synchronous
motors
Reluctance motors
The vector control responds to speed changes with a typical set‐
tling time of < 100 ms.
The vector control responds to load impulses with a typical set‐
tling time of 200 ms.
The vector control is required in the following cases:
– For power-up times 0 → rated speed < 2 s
– For applications with fast and high load impulses
Typically achieves a torque ac‐
curacy of ± 5 % for 15 % ...
100 % of the rated speed
of the rated speed
Commissioning
5.4 Quick commissioning
Vector control with encoder
Vertical conveyor technology
(conveyor belts, roller con‐
veyors, chain conveyors)
Lifters/Lowerers
Stacker cranes
Induction motors
Extends the torque accuracy
of ± 5 % to speeds < 15 % of
the rated speed.
240 Hz
Torque control from speeds = 0.
127