8.4.2.4

Connection through a serial interface

Along with the connection through the PROFIBUS, there is also a facility for data exchange
via the serial interface.
Preconditions
● A serial interface (COM) must be available on the PC from which the connection will be
● An AOP30 must not be connected with the drive.
Connecting cables
Figure 8-30
Settings
1. In STARTER, from Project > Set PG/PC interface, select the Serial cable (PPI) interface.
2. Enter the following settings. The "0" address and the transmission rate 19.2 kbit/s are
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
made.
Assignment, RS232 cable
If this is not available in the dropdown list, you first have to add it using Select.
Note
If the interface cannot be added to the selection menu , the drive for the serial interface
still needs to be installed.
This is located in the following path on the STARTER CD:
\installation\starter\starter\Disk1\SerialCable_PPI\
STARTER must not be active while the driver is being installed.
important here.
8.4 Commissioning with the STARTER commissioning tool
Commissioning
261