Information on telegram interconnections
After changing p0922 = 999 (factory setting) to p0922 ≠ 999, the telegram interconnection is
made and blocked automatically.
Note
Telegrams 20 and 352 are the exceptions. Here, PZD06 in the send telegram and PZD03 to
PZD06 in the receive telegram can be interconnected as required.
When you change p0922 ≠ 999 to p0922 = 999, the previous telegram interconnection is
retained and can be changed.
Note
If p0922 = 999, a telegram can be selected in p2079. A telegram interconnection is
automatically made and blocked. However, the telegram can also be extended.
This is an easy method of creating extended telegram interconnections on the basis of
existing telegrams.
Table 10- 5
Structure of the telegrams
Telegr.
PZD 1
PZD 2
1
STW1
NSET_A
ZSW1
NACT_A
20
STW1
NSET_A
ZSW1
NACT_A_
SMOOTH
352
STW1
NSET_A
ZSW1
NACT_A_
SMOOTH
999
STW1
Free
ZSW1
Free
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
PZD 3
PZD 4
IAACT_
MACT_
SMOOT
SMOOTH
H
PCS7_3
PCS7_4
IAACT_
MACT_
SMOOT
SMOOTH
H
Free
Free
Free
Free
PZD 5
PZD 6
PACT_
SIG_
SMOOTH
NAMUR
PCS7_5
PCS7_6
ALARM_
FAULT_
CODE
CODE
Free
Free
Free
Free
Descriptions of functions
10.2 PROFIBUS
PZD 7
PZD 8
PZD 9
Free
Free
Free
Free
Free
Free
PZD 10
Free
Free
343