● p0809 Copy command data set (CDS)
● p0810 BI: Command data set CDS bit 0
● p0819[0...2] Copy drive data set DDS
● p0820 BI: Drive data set selection DDS, bit 0
● p0821 BI: Drive data set selection DDS, bit 1
9.1.2.2

Using data sets

Copying a command data set
Set parameter p0809 as follows:
1. p0809[0] = Number of the command data set to be copied (source)
2. p0809[1] = Number of the command data to which the data is to be copied (target)
3. p0809[2] = 1
Starts copying.
Copying is finished when p0809[2] = 0.
Copying a drive data set
Set parameter p0819 as follows:
1. p0819[0] = Number of the drive data set to be copied (source)
2. p0819[1] = Number of the drive data set to which the data is to be copied (target)
3. p0819[2] = 1
Starts copying.
Copying is finished when p0819[2] = 0.
Uncommissioned data sets
Drive commissioning can be completed even if uncommissioned data sets (EDS, DDS) are
available.
Uncommissioned data sets are marked as "uncommissioned".
The attributes are displayed in STARTER or in the expert list or OPs.
Activating these data sets is not permitted and any attempt to do so will be rejected with an
error.
Assigning these data sets to a drive data set (DDS) is only possible by means of a
commissioning step (p0009 ≠ 0, p0010 ≠ 0).
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
Operation
9.1 Basic information
291