Order number 6RA80 ..
Rated fan current
Rated fan current
with option L21
Fan air flow
Fan noise level
Dimensions (HxWxD)
Weight (approx.)
3-ph. 950 V AC, 2Q and 4Q units
6RA8096-4MS22
Table 4- 43
Technical data for 3-ph. 950 V AC, 2Q and 4Q units
Common data
Rated
armature supply voltage 1)
Rated
field supply voltage 1)
Electronics power supply, rated supply
voltage
Rated
field DC voltage 1)
Rated frequency
Overload possibility 6)
Closed-loop control constancy
Degree of protection
Protection class
Table 4- 44
Technical data for 3-ph. 950 V AC, 2200 A, 2Q and 4Q units
Order number 6RA80 ..
Rated DC current
Rated DC voltage 1)
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
..88-6LV62
50 Hz
A
60 Hz
50 Hz
A
60 Hz
m
/h
3
50 Hz
dBA
60 Hz
mm
785x268x435
kg
6RA8096-4MV62
V
3-ph. 950 V AC (+15 % / – 20 %)
V
2-ph. 480 V AC (+10 % / – 20 %)
V
2-ph. 380 (– 25 %) to 480 V AC (+10 %); In = 1 A or
1-ph. 190 (– 25 %) to 240 V AC (+10 %); In = 2 A
(– 35 % for 1 min.)
With option L05: 18 to 30 V DC; In = 5 A
V
390
Hz
45 to 65 10)
Max. 1.8x rated DC current
Δn = 0.006% of rated motor speed during operation with incremental
encoder and digital setpoint
Δn = 0.1% of rated motor speed during operation with analog tachometer
or analog setpoint 5)
IP00 acc. to DIN EN 60529
Class I (with protective conductor system) and class III (PELV) to EN
61800-5-1
A
V
..93-4LV62
0.30 9)
0.38
0.81
1.14
1000
70.4
74.2
883x453x505
78
..96-4MS22
2200
1140
..95-4LV62
0.95 9)
1.25
-
2400
80.8
83.2
883x453x505
155
..96-4MV62
2200
1000
Technical data
4.3 Unit data
0.95 9)
1.25
-
2400
80.8
83.2
155
65

Advertisement