X520, X530 Digital Inputs - Siemens SINAMICS DCM Operating Instructions Manual

Dc converter
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Additional system components
7.4 Terminal Module TM31
7.4.3.3

X520, X530 digital inputs

Table 7- 27
Screw terminal X520
Terminal
1
2
3
4
5
6
Table 7- 28
Screw terminal X530
Terminal
1
2
3
4
5
6
DI: Digital input; M: Electronics ground; M1, M2: Ground reference
1)
NOTICE
An open input is interpreted as "low".
Terminal M1 or M2 must be connected in order that digital inputs (DI) can function.
This is carried out by:
1) Providing the ground reference of the digital inputs, or
2) a jumper to M (caution! This removes electrical isolation for these digital inputs).
208
Designation
1)
DI 0
DI 1
DI 2
DI 3
M1
M
Designation
1)
DI 4
DI 5
DI 6
DI 7
M2
M
Technical specifications
Voltage: - 3 to +30 V
Typical power consumption: 10 mA at 24 VDC
Input delay:
- For "0" to "1": typ. 50 µs max. 100 µs
- For "1" to "0": typ. 130 µs max. 150 µs
Electrical isolation: Reference potential is
Terminal M1
Level (including ripple)
High level: 15 to 30 V
Low level: -3 to +5 V
Technical specifications
Voltage: - 3 to +30 V
Typical power consumption: 10 mA at 24 VDC
Input delay:
- For "0" to "1": typ. 50 µs max. 100 µs
- For "1" to "0": typ. 130 µs max. 150 µs
Electrical isolation: Reference potential is
Terminal M2
Level (including ripple)
High level: 15 to 30 V
Low level: -3 to +5 V
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
SINAMICS DCM DC Converter

Advertisement

Table of Contents
loading

Table of Contents