Installation Notes For Installation According To Ul 508C - Siemens SINAMICS DCM Operating Instructions Manual

Dc converter
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

6.10

Installation notes for installation according to UL 508C

Note
The following text has been taken from excerpts from the UL file E203250.
● "Solid state motor overload protection at 110 % of full-load current is provided in each
● "Integral solid state short circuit protection does not provide branch circuit protection.
● Blower motor protection type 3RV1011-0DA1 trimmed to 0.26 A manufactured by
● Blower motor protection type 3FV1011-0EA1 trimmed to 0.38 A manufactured by
● Blower motor protection type 3FV1011-0KA1 trimmed to 1.25 A manufactured by
Table 6- 35
Overview of Frame Sizes (in mm)
Size
Width
A
385
B
385
C
625
D
700
E
780
F
880
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
model", or equivalent.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes", or the equivalent.
Siemens is to be provided for blower motor type R2D225-AP02-09 in drive model sizes C
and D.
Siemens is to be provided for blower motor Type R2D250-AM20-09 in drive model size E.
Siemens is to be provided for blower motor Type RH28M-2DK.3F.1R in Drive model
size F.
Height
Depth
268
210
268
250
268
275
268
310
268
435
448
505
6.10 Installation notes for installation according to UL 508C
Line voltage (V)
400, 480
400, 480, 575
400, 480, 575
400, 480, 575
400, 480, 575
400, 480, 575
Connecting
Output current (A)
15 - 30
60 - 280
400 - 600
760 - 850
1000 - 1200
1600 - 3000
167

Advertisement

Table of Contents
loading

Table of Contents