PDS = parameter data set
Figure 9-5
Using the memory card for series commissioning
The memory card can also be used for series commissioning of several units with the same
parameter assignment.
Procedure:
● Completely commission a "sample" drive. As soon as all of the parameters have been
● Switch-off the system and insert a memory card into the CUD. Switch on the system.
● The parameter assignment is saved on the memory card. If DCC charts are activated in
● Remove the card.
● Insert the card into a CUD that is switched-off and has still not been parameterized.
● When powering up, the parameter assignment is transferred into the CUD and copied
● The card can be removed once the system has powered-up. The CUD that was still not
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
Memory card available: PDS 0 is copied to the card in parallel
p802=20; p803=0; p804=1
p802=20; p803=0; p804=2
For POWER ON, no PDS 0 on the card: PDS 0 is copied from the ROM to the memory card
At POWER ON, PDS 0 on the card: PDS 0 is copied to the ROM
Memory card
Copying parameter data sets
correctly set, carry out "RAM to ROM".
the system, then these as well as the DCC library are also saved on the memory card.
Switch on the system (POWER ON).
both into the ROM as well as also into the RAM. If DCC charts and the DCC library were
saved on the memory card, then these are also copied.
parameterized now has the same parameter assignment as the original "sample" drive.
Operation
9.1 Basic information
297