X521/X531 Alternative Encoder System Interface - Siemens SINAMICS DCM Operating Instructions Manual

Dc converter
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Additional system components
7.2 Sensor Module Cabinet-Mounted SMC30
7.2.3.4

X521/X531 alternative encoder system interface

Table 7- 9
X521/X531 alternative encoder system interface
Pin
X521
1
2
3
4
5
6
7
8
1
X531
2
3
4
5
6
7
8
Max. connectable cross-section: 1.5 mm
When using unipolar HTL encoders, at the terminal block A*, B*, R* must be connected to (jumper) M_Encoder (X531)
Because the physical transmission properties are more robust, the bipolar connection
1)
should always be used. The unipolar connection should only be used if the encoder type
does not output push-pull signals.
CAUTION
When the encoder system is connected via terminals, make sure that the cable shield is
connected to the component. Refer to the section titled "Electrical connection".
NOTICE
The KTY temperature sensor must be connected with the correct polarity.
Hazard due to electric shock
Only temperature sensors that meet the protective separation specifications in EN 61800-5-
1 may be connected to terminals "+Temp" and "-Temp". There is a risk of electric shock if
this is not carefully observed.
180
Designation
A
A*
B
B*
R
R*
CTRL
M
P_encoder 5 V/24 V
M_Encoder
- Temp
+ Temp
Clock
Clock*
Data
Data*
2
DANGER
Technical specifications
Incremental signal A
Inverse incremental signal A
Incremental signal B
Inverse incremental signal B
Reference signal R
Inverse reference signal R
Control signal
Ground
Encoder power supply
Ground for encoder power supply
Temperature sensor KTY84-1C130
Temperature sensor KTY84-1C130
SSI clock
Inverse SSI clock
SSI data
Inverse SSI data
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
.