10.2

PROFIBUS

10.2.1

PROFIBUS connection

Position of PROFIBUS connection and diagnostics LEDs
The PROFIBUS connection and diagnostics LEDs are located on the Control Unit (CUD).
The PROFIBUS connection is established using a 9-pin Sub-D socket (X126). The
connections are electrically isolated.
PROFIBUS connection
Table 10- 3
PROFIBUS connector assignment
Connector
Pin
X126
1
2
3
4
5
6
7
8
9
Module C98043-A7100-L1/L2, Standard/Advanced CUD
Bus connector
The cables must be connected using PROFIBUS bus connectors as these contain the
necessary bus terminating resistors.
Matching PROFIBUS bus connector, Order No. 6GK1500-0FC10:
Figure 10-1
SINAMICS DCM DC Converter
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
Signal name
Technical data
-
Not assigned
-
Not assigned
RxD/TxD-P
RS485 receive/transmit data P (B)
CNTR-P
Control signal (TTL)
DGND
PROFIBUS data ground
VP
Positive supply voltage (5 V +/-10%)
-
Not assigned
RxD/TxD-N
RS485 receive/transmit data N (A)
-
Not assigned
PROFIBUS bus connector
Descriptions of functions
10.2 PROFIBUS
339