Descriptions of functions
10.25 Connecting units in parallel and in series
The speed setpoint and the speed actual value should be entered at the master
The optimization runs should be started at the master converter. The slave converters
Miscellaneous
NOTICE
For a slave converter the i
because for a non-symmetrical current, this would then respond at the slave.
452
As long as the master does not receive a switch-on command, the slaves stay in
operating state o10.0 (wait for switch-on from the master).
If the master receives a switch-on command, then it automatically transfers this to the
slaves. Then, all units carry out their switch-on sequence, i.e. they attempt to go into
operating state o0. However, the master waits in operating state o1.7 until all slaves
have reached operating state o0 (exception: n+m operation for a 6-pulse parallel
connection)
If a slave leaves operating state o0, then the master outputs fault message F60044
(exception: n+m operation for a 6-pulse parallel connection)
converter.
must be connected and ready for operation at this point.
t monitoring of the motor should be deactivated (p50114=0),
2