Parameterizing the inverter enable

The inverter can be enabled from the interface, operator panel or terminal strip.
Set the key-actuated switch into the "Remote" setting ⇒ the inverter is enabled via
terminal strip X100:36A/36C using an H signal. If the key-actuated switch is in the
"Local" setting, then the inverter is always enabled. The assignment can be
changed as follows:
P140, P141
1,2,3,4,5
4.2.7

Changeover, remote/local control

SIMOVERT MV is equipped with a key-actuated switch, which is used to toggle
between remote- and local control (pushbutton in the door, OP2 operator panel).
The status of the key-actuated switch is interrogated in the software. In the
standard condition (the key-actuated switch is in the "Remote" setting), the "Basic"
settings for the control signal and setpoint sources are active (also refer to Section
4.4). If the key-actuated switch is in the on position ("Local" setting), the "Standby"
settings are active for the control signal- and setpoint sources.
In order that the key-actuated switch has the required function, the "Standby"
setting of the control signal- and setpoint sources must be selected, so that the
local control devices are active (pushbutton in the door, OP2 operator panel). This
corresponds to the factory setting.
52
1 = Interface
2 = Operator panel
3 = Terminal strip X100:A36/C36
4 = 1 / permanently enabled
5 = 0 / permanently inhibited
Siemens AG
SIMOVERT MV
Commissioning Instructions
4
6SE8004-0BH76