Connecting
6.9 Assignment of terminals and connectors
With option L05
Table 6- 24
Terminal type, electronics power supply
Type
Connection capacity
Stripped length
Tightening torque
Table 6- 25
Assignment of terminals for the electronics power supply
Terminal
Function
XP24V
+
24 V infeed
-
Module C98043-A7107, Power Interface 400 - 600 V or C98043-A7108, Power Interface 690 - 950 V
6.9.4

Fan

Table 6- 26
Terminal type, fan connections for units ≥ 400 A with forced ventilation
Type
Connection capacity
The connecting leads must be insulated up to the point where they meet the terminal
enclosure.
Table 6- 27
Terminal assignment for fan connection
Terminal
Function
4U1
400 to 460 V
4V1
infeed
4W1
Protective conductor PE
or
4U1
230 V infeed
4N1
Protective conductor PE
156
MSTB 2.5/CIF plug-in terminal
Rigid/flexible/conductor sizes (mm
Flexible with end sleeve with/without plastic sleeve: 0.25-2.5/0.25-2.5 mm
7 mm
0.5 - 0.6 Nm
Technical specifications
18 V to 30 V DC; current consumption 1 A ... 5 A
Recommended conductor cross-section 1.5 mm
Internal protection with F200 fuses (6.3 A, time-lag),
External protection 6 A ... 16 A, B or C characteristic
DFK-PC4 plug-in terminal
Rigid/flexible/conductor sizes (mm
Technical data
3-ph. 400 V to 460 V AC
For additional data, refer to the technical data in Chapter 4.
1-ph. 230 V AC
For additional data, refer to the technical data in Chapter 4.
/mm
/AWG): 0.2-2.5 / 0.2-2.5 / 24-12
2
2
/mm
/AWG): 0.2-4 / 0.2-4 / 24-10
2
2
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
2
2
SINAMICS DCM DC Converter