Descriptions of functions
10.7 Switch on, switch off, enable
Procedure for shutting down the drive:
1. Apply the "Shutdown" command (e.g. using the "Switch on/Shutdown" terminal).
2. Deceleration along the ramp-function generator ramp
3. Wait until n < nmin (p50370, p50371).
4. The "Close holding or operational brake" (r53210.0 = 1) signal is output.
5. The brake-closing time (p50088) is awaited.
6. The ramp-function generator and n controller are disabled.
7. Reduction in armature current
8. The armature firing pulses are disabled.
9. The "Line contactor closed" relay (terminal XR1-109 and XR1-110) drops out.
10. Operating state o7.0 or higher is reached.
11. The wait time for field-current reduction (p50258) elapses.
12. The field is reduced to a parameterizable value (p50257).
"Switch on/Shutdown" overview
p50087
Brake-release time (positive in this case)
p50088
Brake-closing time
p50258
Wait time for automatic field-current reduction
Figure 10-33 Switch on/Shutdown
● An internal interlock becomes active once n < nmin (r50370, r50371) for the first time.
● Whether level triggering or pulse triggering is selected has an overriding effect on "Switch
396
This stops the drive from attempting to decelerate again if the motor is rotated by external
influences; the n < nmin message then disappears.
on", "Shutdown", and "Creep".
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619