Descriptions of functions
10.2 PROFIBUS
6. Select the Publisher DP address in the "PROFIBUS address" column.
7. The "I/O address" column displays the start address for every DO.
8. The "Slave-to-salve communication - Overview" tab shows you the configured slave-to-
356
All PROFIBUS DP slaves are listed here from which actual value data can be requested.
It also provides the possibility of sharing data via slave-to-slave communication within the
same drive group.
Select the start address of the data of the DO to be read. This is 200 in the example.
If the complete data of the Publisher are not read, set this via the "Length" column. You
may also offset the start address for the request so that data can be read out in the
middle of the DO telegram.
Figure 10-10 Configuring the slave-to-slave communication nodes
slave communication relationships which correspond to the current status of the
configuration in HW Config.
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619
SINAMICS DCM DC Converter