Transportation, unpacking, installation

5.2 Installation

5.2
Installation
Failure to lift the unit properly can lead to physical injury or material damage.
The unit should only be lifted with suitable equipment (work gloves should be used) and by
appropriately qualified personnel.
In order to prevent the enclosure from becoming deformed when lifting units with a rated
DC current above 720 A, no horizontal forces may be exerted on the lifting eyes.
The user assumes responsibility for installing the converter unit, motor, transformer, and
other units in accordance with safety regulations (e.g. EN, DIN, VDE) and all other relevant
national or local regulations affecting conductor dimensioning, protection, grounding,
disconnectors, overcurrent protection, and so on.
The unit must be installed in accordance with safety regulations (e.g. EN, DIN, or VDE) as
well as all other applicable national or local regulations. Grounding, conductor
dimensioning, and the relevant short-circuit protection work must be carried out correctly in
order to ensure operational safety.
Options for lifting units with a 1500 to 3000 A rated DC current
Figure 5-1
UL 508 C-compliant cabinet installation for a SINAMICS DC MASTER
● If this unit is to be installed in a cabinet, the cabinet must be sufficiently ventilated and of
● To install a unit, the minimum dimensions of the cabinet must be 2,200 mm x 600 mm x
70
CAUTION
Options for lifting units with 1500 - 3000 A currents
"type 1" in accordance with standard UL 508 C.
600 mm (H x W x D).
Operating Instructions, 1.2012, C98130-A7066-A1-05-7619