Srx5400 Services Gateway Rack Size And Strength Requirements; Spacing Of Rack Mounting Bracket Holes For The Srx5400 Services; Connection To Building Structure For The Srx5400 Services Gateway; Clearance Requirements For Srx5400 Services Gateway Airflow And Hardware Maintenance - Juniper SRX5400 Hardware Manual

Services gateway
Hide thumbs Also See for SRX5400:
Table of Contents

Advertisement

SRX5400 Services Gateway Rack Size and Strength Requirements

Copyright © 2014, Juniper Networks, Inc.
Chapter 4: Preparing the Site for the SRX5400 Services Gateway Installation
Figure 16: Typical Open-Frame Rack
The rack requirements are described in the following topics:
SRX5400 Services Gateway Rack Size and Strength Requirements on page 37
Spacing of Rack Mounting Bracket Holes for the SRX5400 Services Gateway on page 38
Connection to Building Structure for the SRX5400 Services Gateway Rack on page 39
Clearance Requirements for SRX5400 Services Gateway Airflow and Hardware
Maintenance on page 39
The size, strength, and location of the rack must accommodate the services gateway's
weight and external dimensions. The location of the rack must allow for the clearance
requirements specified in .
The chassis is 17.37 in. (44.11 cm) wide. The services gateway is designed for installation
in a standard 19-in. rack, as defined in Cabinets, Racks, Panels, and Associated Equipment
(document number EIA-310-D) published by the Electronics Industry Association
(
http://www.eia.org
). The spacing of the holes between the left and right front-mounting
flanges and center-mounting brackets is 18.31 in (465 mm) apart. However, the inner
edge of the rack rails must allow sufficient space for the width of the chassis.
37

Advertisement

Table of Contents
loading

Table of Contents